Carlo Gavazzi EM24
Configuration
Check that the Carlo Gavazzi meter is set to read both import and export power. An unsuitable mode may lead to:
Missing readings of feed-in, or
Feed-in being counted as offtake (on top of the ‘actual offtake’)
You can set this in the ‘MEASurE’ configuration menu on the energy meter. This should be set to ‘b’.
Warning
Warning
This setting may not be present on MID certified models (model numbers ending in PFA and PFB).