For the complete documentation index, see llms.txt. This page is also available as Markdown.

Active power control and fallback

Setting the feed-in management mode so curtailment arrives, and configuring the inverter's own fallback for a loss of communication

An SMA inverter decides for itself where it expects its active power limit to come from. That one setting determines whether the EMS can curtail the inverter at all, and whether the inverter protects itself when the EMS falls away.

Set the feed-in management mode

In the inverter's web interface, logged in as Installer:

Device parameters > System and device control > Inverter > Active power configuration

Set Operating mode of active power setpoint to External setpoint.

In the Dutch interface: Apparaatparameters > Installatie- en apparaatbesturing > Omvormer > Configur.werk.vermogen — set Bedr.mod. voorinstel. act. vermogen to Externe instelling werkelijk vermogen.

This is the only setting under which the fallback works. The inverter keeps a separate channel for an external controller, and both the setpoint the EMS writes and the fallback that guards it live on that channel. Choose a direct setpoint mode instead (in watts or in percent) and the EMS can still curtail, but the fallback settings become decoration: the inverter never consults them.

The percentage is relative to the configured maximum

The limit is a percentage of the inverter's configured maximum active power, not of its nameplate rating. On an inverter rated 125 kW but configured to a maximum of 70 kW, 50 % means 35 kW.

That is usually what you want: a deliberate power cap keeps working and the EMS curtails within it. Be aware that changing the maximum active power also changes what every percentage means.

Configure the fallback, on the right channel

The inverter can limit itself once it stops receiving setpoints, for example when the EMS controller loses its connection. This is optional and switched off by default.

Device parameters > System and device control > Plant control and fallback mode

In the Dutch interface: Installatie- en apparaatbesturing > Installatiebesturing en terugvalmodus.

Channel 1 left on "keep values", the fallback configured on channel 2

Set on the channel that carries the setpoint:

Setting
Value

Fallback mode

Apply fallback values (Terugvalw. overnemen)

Fallback value of maximum active power

agree with the customer

Fallback value of minimum active power

0 %

Timeout

30 s or more

Leave the other channel on Keep values. A fallback armed there fires the moment you switch it on, because nothing feeds it.

Choose the fallback power deliberately. Too low costs production on every brief communication hiccup; too high offers little protection.

Finding out which channel is yours

Give the two channels a clearly different fallback value, for instance 15 % on one and 40 % on the other, arm both, and then cut the communication. The power the inverter settles on tells you which channel was being fed. Put the other one back on Keep values afterwards.

Set the timeouts long enough

The EMS refreshes its setpoint roughly every five seconds. Two timers decide how long the inverter waits before the fallback takes over, and both have shipped far too short on units we have seen: 0,3 s and 3 s respectively. Anything under 15 seconds produces false fallbacks on a single missed message.

To find them, switch the parameter list to channel names (the Channel button, then Grouping: Off) and search for WCtlCom:

Channel
Meaning

Inverter.CtlComCfg.WCtlCom.TmsOutPrc

timeout before the fallback engages

Inverter.WModCfg.WCtlComCfg.Dyn.WTms

response time for the external setting

How it behaves

Measured end to end on a Sunny Tripower 125, with the EMS steering and the fallback set to 15 % on channel 2:

Situation
Power

EMS steering normally

34,9 kW

communication cut

drops through 19,0 kW

fallback in force

10,5 kW, held flat

communication restored

back to 35,0 kW within ~15 s

Recovery needs no intervention. Once the EMS starts writing again, the inverter follows within seconds.

Verify

Change the inverter's IP address so the EMS can no longer reach it, or set the device to non-controllable in the platform. Either cuts the setpoint at the source. Within the timeout the inverter should drop to the fallback power; undo the change and it should return to normal within about fifteen seconds.

This is also the check that tells you the fallback sits on the right channel. Does the power not move at all, then it is configured on the channel the EMS does not feed.

The fallback cannot be set from the platform

Every fallback setting lives on the inverter itself. The fallback value and both timeouts carry SMA's Grid Guard marking, so writing them needs a Grid Guard session opened with the installer's personal code. That code is personal, and it would grant write access to every grid parameter on the device, so the EMS never uses it. The Sunny Tripower 125 therefore has no fallback setpoint field in the platform: configure the fallback in the inverter's own interface, as described above.

What the EMS does contribute is the part only it can do. While either channel has a fallback armed, it refreshes the setpoint every cycle, so the inverter's timeout elapses on a real loss of communication and not because our own write interval happened to be longer.

Last updated