For the complete documentation index, see llms.txt. This page is also available as Markdown.

IO module emergency stop

Placing, wiring and configuring a Moxa IO module so a DSO RTU emergency stop is also executed physically, in hardware.

For installations that require a physical emergency stop, the DSO RTU emergency-stop signal can drive one or more relay outputs on a Moxa IO module. When the grid operator triggers an emergency stop, the EMS drives the configured relay output(s) to their stop state. Those relays are wired into the installation's emergency-stop circuit.

This is the hardware layer described in How DSO RTU works. It is in addition to the software stop; assets are always curtailed in software as well.

lightbulb

Use the IO module when a stop must be enforced independently of the asset's own communication, for example to drive an external contactor, an EPO loop, or the emergency-stop input of switchgear.

The hardware

  • Module: Moxa ioLogik E1214 with 6 digital inputs (DI) and 6 relay outputs (DO).

  • Communication: Modbus TCP/IP.

  • The relay outputs are potential-free contacts that you wire into the installation's safety/stop circuit. The digital inputs are available for status feedback if needed.

Place the IO module

Where the module goes, and how many modules you need, depends on the physical layout of the installation. A relay must be wired to the asset or switchgear it has to stop, so a module is placed close to those assets; an installation spread over several cabinets therefore needs a module in each cabinet that has to be stopped.

See Installing the IO modules for the full placement and cabling guidance. Note each module's IP address, port and Modbus slave ID, since you need them when adding the device on the platform.

Wire the emergency stop

  • Assign one or more relay outputs to each emergency-stop action you want to enforce (production and/or consumption). Several outputs can act on the same action, useful to stop multiple assets or cabinets at once.

  • Wire each relay into the emergency-stop / EPO input of the asset it has to stop.

  • How a stop maps to the relay depends on the relay actuation mode you choose per output (normally open / normally closed and what the closed contact means). The contacts can be wired so that an active stop energizes or de-energizes the relay (see Behaviour).

Configure the IO module on the platform

1. Add the IO module as a device

  • Device type: IO Extension

  • Brand: Moxa, model: ioLogik E1214

  • Connection: Modbus TCP/IP, with the module's IP address, port and slave ID.

2. Assign the emergency-stop output(s)

Open the device's Ports page (or Project settings → Telecontrol) and, for each relay output (DO) you wired, set its function to Telecontrol emergency switch and choose:

  • Action: Injection (driven by emergency stop production) or Consumption (driven by emergency stop consumption).

  • Relay actuation mode: how the contacts are wired (normally open / normally closed) and what the closed contact means. This determines whether an active stop energizes or de-energizes the relay (see Behaviour).

You can assign multiple outputs to the same action (for example one per cabinet), each with its own actuation mode, and you can configure only the action you need.

The configuration is delivered to the EMS controller automatically as part of the project configuration; no manual controller changes are needed.

Behaviour

An Injection output acts on emergency stop production; a Consumption output acts on emergency stop consumption. When the relevant stop is active, the EMS commands the asset OFF; when it is cleared, the asset is allowed to run. The relay actuation mode translates that into the digital-output value, so the relay can be wired either way:

Relay actuation mode

Relay on active stop

Relay when cleared

NO-ON: NO contacts, on when closed (default) → de-energize to stop

De-energized (open, 0)

Energized (closed, 1)

NC-OFF: NC contacts, off when closed → de-energize to stop

De-energized (0)

Energized (1)

NO-OFF: NO contacts, off when closed → energize to stop

Energized (closed, 1)

De-energized (open, 0)

NC-ON: NC contacts, on when closed → energize to stop

Energized (1)

De-energized (0)

The relay state is re-evaluated every control cycle (≈ 1 second), so it follows the DSO RTU state with sub-second latency. When several outputs are mapped to the same action they are all driven together. Outputs that are not assigned as a telecontrol emergency switch are unaffected and remain available for other uses.

Safety and requirements

Monitoring and troubleshooting

If a DSO RTU emergency stop is active but the EMS cannot actuate the configured output (for example the module is offline or its relay state cannot be read back), a critical incident is raised. It clears automatically once the module is reachable again and the output is confirmed.

If you see this incident:

  • Check network connectivity to the IO module (IP, port, slave ID).

  • Verify the module is powered and reachable over Modbus TCP.

  • Confirm the module is configured as managed.

Voltmasters tests the hardware emergency stop end to end during commissioning.

Last updated